IEC 60870-5-104 (Power Telecontrol)

IEC 60870-5-104 — the telecontrol standard for transmission, distribution, and generation systems (TCP 2404). Because RTUs and gateways push measurements and statuses upstream, the gateway holds the values and then exposes them to tags.

SituationWhich card to use
RTU · Grid Gateway · Remote MonitoringIEC-104 (this page)
Substation IED · Protection RelaysIEC 61850
North American utility SCADADNP3
General Instruments · InvertersModbus TCP

Registration Form Input Values​

Input FieldWhat to EnterExample
IP AddressRTU · Gateway address10.20.30.40
PortStandard 24042404
Collection PeriodInterval for reading from the cache (ms)1000

Options​

OptionDefaultDescription
common-address1ASDU common address. Must match the value configured on the equipment
general-interrogationOnRequests all values once immediately after connection
If common-address is different, "the connection works but no values appear"

If TCP connects and STARTDT is exchanged but tags remain empty, this is almost certainly the issue. Check the ASDU address in the equipment's configuration screen and align it.


Tag PLC Address Notation — IOA​

Tag's PLC Address = IOA (Information Object Address, integer).

FormatMeaning
1001IOA 1001
13:1001Ignores the preceding type identifier and reads as IOA 1001

We accept the 13:1001 format so that you can paste tag lists from other SCADA systems directly — since the type is determined from the value itself, this is at least harmless.


Not Polling — "Hold & Provide"​

접속 ─▶ STARTDT ─▶ 일반심문(전체 값 요청)
│
RTU 가 값이 바뀔 때마다 밀어 준다
▼
게이트웨이가 IOA 별로 최신값을 담아 둔다
│
수집 주기마다 태그가 그 캐시를 읽는다

🔴 Shortening the collection period does not increase RTU load. The period is merely the interval at which the cache is read; the rate at which values arrive is determined by the RTU. Conversely, if the RTU doesn't send, no matter how short you set the period, values won't refresh.


When Things Don't Work​

SymptomWhat to Check First
Connection fails entirely2404 firewall, whether the RTU allows this gateway's IP
Connection works but all values are emptycommon-address, and whether general-interrogation is enabled
Only some IOAs are emptyWhether the RTU actually sends that IOA (band configuration)
Values stop updatingThe RTU session may have died — try disconnecting and reconnecting

→ Connection Status Check · Troubleshooting